Détails du produit
Lieu d'origine: Chine
Nom de marque: BOEN FIRE
Certification: ISO9001、CCCF、CNEX、SIL2
Numéro de modèle: GT-CDI2950DEx
Conditions de paiement et d'expédition
Quantité de commande min: 1
Prix: Négociable
Délai de livraison: 15-20 jours
Conditions de paiement: LC, T/T
Certification: |
CCC, explosion-proof (CNEx22.1282X), type approval & inspection report, compliant with GB standards |
Détection: |
Combustion catalytique (échangeable à chaud), 3 ~ 100 % LIE, réponse ≤ 30 s, diffusion naturelle |
Capteur: |
Durée de vie de 3 ans, pour méthane/propane/hydrogène |
Alarme: |
Seuils 25 %/50 % LIE, alarme sonore (75 ~ 95 dB)/visuelle (70 Cd) en option |
Communication: |
4-20mA + RS485 (Modbus), transmission ≤1000m |
Matériel: |
DC18~28V, -40~70℃, IP66, boîtier métallique (2kg), filetage G3/4" |
Affichage et fonctionnement: |
Écran LCD, télécommande infrarouge (≤5m), réglage adresse/seuil d'alarme |
Entretien: |
Calibrage tous les 6 mois, vérification annuelle, remplacement du capteur avec recalibrage |
Certification: |
CCC, explosion-proof (CNEx22.1282X), type approval & inspection report, compliant with GB standards |
Détection: |
Combustion catalytique (échangeable à chaud), 3 ~ 100 % LIE, réponse ≤ 30 s, diffusion naturelle |
Capteur: |
Durée de vie de 3 ans, pour méthane/propane/hydrogène |
Alarme: |
Seuils 25 %/50 % LIE, alarme sonore (75 ~ 95 dB)/visuelle (70 Cd) en option |
Communication: |
4-20mA + RS485 (Modbus), transmission ≤1000m |
Matériel: |
DC18~28V, -40~70℃, IP66, boîtier métallique (2kg), filetage G3/4" |
Affichage et fonctionnement: |
Écran LCD, télécommande infrarouge (≤5m), réglage adresse/seuil d'alarme |
Entretien: |
Calibrage tous les 6 mois, vérification annuelle, remplacement du capteur avec recalibrage |
GT-CDI2950DEx Industrial and Commercial Point-Type Flammable Gas Detector
![]()
1.Product Overview
This product is an explosion-proof device, suitable for Zone I and Zone II environments where there may be leakage or explosion hazards of flammable or toxic and harmful gases in industries such as petroleum, chemical engineering, gas storage stations, and wine factory production workshops. It is not applicable to Zone 0 or underground coal mine environments. The detector can conduct safe detection and give advance alarms for gas leakage accidents.
The detector features TFT liquid crystal display, infrared remote control, three-wire 4mA-20mA output, RS485 bus communication (Modbus RTU protocol), and passive contact output functions.
2.Product Features
(1) Adopts a segment LCD display with infrared remote control function, making debugging convenient.
(2) Uses a thermistor sensor, enabling maintenance personnel to replace all sensors in the entire site easily.
(3) Equipped with sound and light alarm function. When detecting combustible gas leakage, the detector will issue a harsh sound and light alarm to avoid.
(4) Has zero-point correction function, which can avoid measurement errors caused by zero-point drift.
(5) Features a standard RS485 interface based on the Modbus (RTU) protocol.
(6) Can be matched with JB-QB-CH210 combustible gas alarm controller, PLC, DCS and other systems for use.
(7) Adopts a single-chip microcomputer processing system, which has stable performance, strong anti-interference ability and low power consumption.
3.Main Technical Data
| Item | Content |
| Detection Principle | Catalytic Combustion (Hot-swappable Type) |
| Sampling Method | Natural Diffusion |
| Detection Range | 3~100%LEL |
| Resolution | 1%LEL |
| Response Time | ≤30s |
| Measurement Error | Full Scale ±3%LEL |
| Resolution | 1%LEL |
| Low Alarm Value | 25%LEL |
| High Alarm Value | 50%LEL |
| Audible Intensity (Optional) | 75~95dB |
| Flash Intensity (Optional) | 70cd |
| Applicable Gas | Methane, Propane, Hydrogen |
| Display Mode | LCD Display |
| Signal Transmission | 4mA~20mA Output, Standard RS485 Interface, Alarm Relay and Audible-Visual Alarm Output |
| Signal Bus Transmission Distance | ≤1000m |
| Working Voltage | DC18V~DC28V (Rated: DC24V) |
| Power Consumption | <2W |
| Temperature Range | -40℃~+70℃ |
| Humidity Range | 0~95%RH (No Condensation) |
| Pressure Range | 86kPa~106kPa |
| Shell Material | Metal |
| Overall Weight | 2kg |
| Installation Thread | G3/4" |
| Dimensions | 150×177×72 (mm) |
| Protection Class | IP66 |
| Explosion-proof Mark | Ex d IIC T6 Gb/Ex tD A21 IP66 T80℃ |
| Note | Audible and Flash Functions are Optional |