CDINDUSTRY ( INTERNATIONAL ) . INC marketing@cdindustry-og.com 86-23-86636683
Get Best Price quote
CDINDUSTRY ( INTERNATIONAL ) . INC Company Profile
products
Home > products > IR Flame Detector > Petroleum Industry Ex IR Flame Detector ⅡC ⅢC For Multi Fuel Sensing

Petroleum Industry Ex IR Flame Detector ⅡC ⅢC For Multi Fuel Sensing

Product Details

Place of Origin: CHINA

Brand Name: BOEN FIRE

Certification: ISO9001、CCCF、CNEX、SIL2

Model Number: JSY-F301-A

Payment & Shipping Terms

Minimum Order Quantity: 1

Price: Negotiable

Delivery Time: 15-20 days

Payment Terms: L/C,T/T

Get Best Price
Chat Now
Product Details
Highlight:

Ex IR Flame Detector

,

Petroleum Industry IR Flame Detector

,

Multi Fuel Sensing Flame Detector

Spectrum Range:
3.8um 4.4um
Response Time:
N-heptane ≤15s
Explosion Proof:
Ex Db ⅡC T6 Gb、Ex Tb IIIC T80℃ Db
Operating Current:
≤20mA
Color:
Silver, Red (Customizable)
Weight:
1.35kg (2.976lbs)
Relay Contact Capacity:
1A/AC 125V 2A/DC 30V
Material:
Cast Aluminum (stainless Steel Is Optional)
Spectrum Range:
3.8um 4.4um
Response Time:
N-heptane ≤15s
Explosion Proof:
Ex Db ⅡC T6 Gb、Ex Tb IIIC T80℃ Db
Operating Current:
≤20mA
Color:
Silver, Red (Customizable)
Weight:
1.35kg (2.976lbs)
Relay Contact Capacity:
1A/AC 125V 2A/DC 30V
Material:
Cast Aluminum (stainless Steel Is Optional)
Product Description

Petroleum Industry Ex IR Flame Detector ⅡC ⅢC  Multi-Fuel Sensing 

 

 

1. Product Overview

 

The JSY-F301-A is a two-infrared flame detector dedicated to tunnels. As an explosion-proof multi-spectral flame detector, it is suitable for various fuel types in the petroleum industry and can provide early warnings.​

 

Equipped with two infrared wavelength sensors, an ultraviolet sensor, and a sapphire optical filter, this detector has a high response to combustion flames from various fuel types in the petroleum industry. It collects multiple signal data and, through unique time-domain and frequency-domain signal processing, as well as the Fourier fuzzy algorithm, combined with comprehensive judgment and processing of interference source logic, eliminates the interference of ambient light and thermal body radiation, maximizing the suppression of false alarms. Thus, it is well-suited for petroleum industry environments with multiple false alarm sources, both indoor and outdoor. The special fire signal processing algorithm and multi-sensor technology have significantly improved the detector's sensitivity, enabling it to operate in harsh industrial environments such as high/low temperatures and high humidity in the petroleum sector.

 

2. Product Features

 

(1) Judges flames through multi-frequency infrared, ultraviolet, time-domain and frequency-domain analysis ​

(2) Sensitivity can be adjusted on-site ​

(3) Works with various fuel types ​

(4) Comes with self-learning function and resists electromagnetic interference​

(5) Prevents false alarms and has a solar blind feature​

(6) Is dustproof, explosion-proof, anti-corrosion and waterproof​

(7) Complies with national standards GB 15631 - 2008 and GB 12791 - 2006 

 

3. Application 

 

(1) Oil exploration and production sites​

(2) Petrochemical product manufacturing, storage, and transportation​

(3) Oil refineries and processing plants​

(4) Petroleum storage warehouses and logistics hubsThese applications cover a wide range of petroleum industry activities, and the detector's robust features make it an ideal choice for ensuring safety across these different settings.​

(5) Pipeline transportation facilities and pumping stations

 

4.Main Technical Data

 

Nominal Voltage 24V DC (18V DC~36V DC)
Operating current ≤20mA
Alarm current ≤25mA / DC 24V
Ambient temperature -10~+55°C
Ambient humidity ≤95% relative humidity without condensation
Spectral response 3.8um  4.4um
Fire response time N-heptane ≤15s
Adjustable sensitivity Level I (The default level is Level I at the factory and it is locked.)
Detection angle Vertical viewing angle: 90°; Horizontal viewing angle: 120°
Protection level IP67
Output mode Standard relay output (fault, fire alarm), 4-20mA (optional)
Relay contact capacity 1A/AC 125V  2A/DC 30V
Material Cast aluminum (stainless steel is optional)
Implementation standard GB 15631-2008  GB 12791-2006
Dimensions φ100mm/H165mm(φ3.94in/H6.50in)
Weight (kg / lbs) 1.35kg (2.976lbs)
Color Silver, Red (Customizable)
Cable outlet thread Standard G3/4, two pieces
Explosion-proof mark Ex db C T6 Gb,Ex tb IIIC T80 Db
Detection distance Fuel Fire source size Details
N-Heptane 0.3mx0.3m(lft.x1ft.) 50m(164ft.)
Petrol 0.3mx0.3m(1ft.x 1ft.) 40m(131ft.)
Diesel fuel 0.3mx0.3m(1ft.x lft.) 35m(114ft.)
Kerosene 0.3mx0.3m(lft.x1ft.) 35m(114ft.)
Ethanol 0.3mx0.3m(lft.x lft.) 30m(98ft.)
Methane 0.5mx0.2m(1.7ft.x0.7ft.) 30m (98ft.)
Sheet of paper 0.3mx0.3m(1ft.x 1ft.) 25m(82ft.)

 

5.Indicator Lights
The JSY-F301-A flame detector is equipped with three status indicator lights, which are used to indicate its working status.

 

Status Indicator light
Operation Indicator Light (Green) Always on
Alarm Confirmation Indicator Light (Red) It blinks for early warning and is always on for an alarm.
Fault Indicator Light (Blue) When a fault occurs, the blue light is always on (and the red light goes out). When the device is powered on, it blinks to show the self-checking and self-adaptive status.

 

6.Complete Product Set

 

Name Quantities Unit of measure
JSY-F301-A
Point-type Infrared Flame Detector
1 piece
Instruction Manual 1 copy
Explosion-proof Certificate 1 copy
Mounting Bracket 1 item
Fastenings 1 item
M8 Nut 1 piece
M8x45 Hexagon Socket Head Cap Screw 1 piece
M8x25 Hexagon Socket Head Cap Screw 1 piece
Flame Detection Remote Controller YC-F1 1 piece per batch