CDINDUSTRY ( INTERNATIONAL ) . INC marketing@cdindustry-og.com 86-23-86636683
CDINDUSTRY ( INTERNATIONAL ) . INC Company Profile
products
Home > products > Pipeline Leakage Detector > Industrial Grade Open-path Laser Natural Gas Leakage Detector for Accurate Detection

Industrial Grade Open-path Laser Natural Gas Leakage Detector for Accurate Detection

Product Details

Place of Origin: CHINA

Brand Name: BOEN FIRE

Model Number: Discovery - O1

Payment & Shipping Terms

Minimum Order Quantity: 1

Price: Negotiable

Delivery Time: 15-20 days

Payment Terms: L/C,T/T

Get Best Price
Chat Now
Product Details
Highlight:

Industrial Grade Leakage Detector

,

Natural Gas Pipeline Leakage Detector

,

Open path Gas Leakage Detector

Product Description

Open-path Laser Natural Gas Leakage Detector



1.Product Overview


The open-path laser natural gas leakage detector Discovery-01 is a new type of gas detection instrument developed by our company. It is an outdoor-use product. It is currently a technologically advanced open-type laser gas detector and has been installed in multiple challenging and harsh environment industrial applications. Discovery-01 is a high-precision instrument designed based on the principle that methane gas has an absorption effect on specific wavelengths of laser (TDLAS). It adopts long-life laser and micro-control technology, combined with excellent SMD manufacturing process. It has excellent repeatability and temperature/humidity characteristics, as well as a long service life and convenient operation.



2.Product Features


(1) Unique output waveform, pulse duration is only 1 to 2 ms, strong anti-interference ability.

(2) With complete self-check function, corresponding fault alarm signals are output.
(3) High measurement accuracy, stable performance, long service life.

(4) 4-20mA standard analog signal output.

(5) Professional matching installation bracket, easy and convenient for on-site installation.

(6) Fast response speed, high sensitivity.

(7) The measurement distance is relatively long, the farthest can reach 200m. 



3. Application 


The petroleum, petrochemical, oil refining, chemical, metallurgical industries, and power sectors.



4. Main Technical Data


Discovery - O1

Item

Description

Detection of gases

CH4

Measuring range

0-5%VOL-m or 0-100%LEL-m

Response time

<0.1s

Detection distance

<200m

Sensitivity

5ppm.m

Laser wavelength

1653.7nm

Measuring laser safety level

Classl

Indicator laser safety level

Class IIIR

Operating voltage

14-36VDC

Power consumption

≤5W

Electrical characteristics

4-20mA Current or RS485 Output

0mA Trouble

2mA Suppressed current

2.5mA Detection of blocked optical path

3mA Optical mirrors are dirty

4- 20mA Normal operation (0-5LEL.m)

21mA Out of range

Electrical interface

M20*1.5

Fixing method

Wall or column mounted

Housing material

316 stainless steel

Operating temperature

-40℃~+70℃

Operating humidity

≤98%RH(non-condensing)

Atmospheric pressure

86kPa~106kPa

Storage environment

Storage temperature -20℃~+30℃,Relative humidity ≤60%RH,No corrosive substances on site, etc.

Wind speed

Not more than 8m/s

Protection class

IP67

Explosion protection marking

Exd IICT6 Gb



5. FQA


Why choose open-path gas detection?


(1) A wider coverage area can detect any leakage.
(2) Detection is carried out within a linear area ranging from 0 to 200 meters.
(3) The response is fast, allowing for understanding of the cumulative concentration of the gas cloud.
(4) It does not cause poisoning, no calibration is required, and the maintenance volume is small.
(5) It can understand the diffusion of the gas when the wind direction changes.