CDINDUSTRY ( INTERNATIONAL ) . INC marketing@cdindustry-og.com 86-23-86636683
Get Best Price quote
CDINDUSTRY ( INTERNATIONAL ) . INC Company Profile
products
Home > products > UV IR Flame Detector > Quad Band Flame Detector UV IR 24V DC CNEX For Power Plants

Quad Band Flame Detector UV IR 24V DC CNEX For Power Plants

Product Details

Place of Origin: CHINA

Brand Name: BOEN FIRE

Certification: ISO9001、CCCF、CNEX、SIL2

Model Number: JSY-F401

Payment & Shipping Terms

Minimum Order Quantity: 1

Price: Negotiable

Delivery Time: 15-20 days

Payment Terms: L/C,T/T

Get Best Price
Chat Now
Product Details
Highlight:

Flame Detector UV IR 24V

,

Quad Band UV Flame Detector

,

CNEX Flame Detector UV IR

Spectrum Range:
3.8um 4.4um 5.3um 185-260nm
Response Time:
N-heptane ≤15s
Cone Of View:
120°
GBS:
GB12791、GB15631、GB3836
Explosion Proof:
Ex Db ⅡC T6 Gb、Ex Tb IIIC T80℃ Db
IP Proof Level:
IP67
Operating Current:
≤20mA
Weight:
1.35kg (2.976lbs)
Spectrum Range:
3.8um 4.4um 5.3um 185-260nm
Response Time:
N-heptane ≤15s
Cone Of View:
120°
GBS:
GB12791、GB15631、GB3836
Explosion Proof:
Ex Db ⅡC T6 Gb、Ex Tb IIIC T80℃ Db
IP Proof Level:
IP67
Operating Current:
≤20mA
Weight:
1.35kg (2.976lbs)
Product Description

CNEX UV IR Quad-Band Flame Detector 24V DC ≤15s Response Time


Quad Band Flame Detector UV IR 24V DC CNEX For Power Plants 0


1.Product Overview


JSY-F401 is an explosion-proof multi-spectral flame detector,applicable to multiple fuel types and can provide early alarms.


The detector is equipped with three infrared wavelength sensors, one ultraviolet sensor, and a sapphire optical filter. It has extremely high response characteristics to the combustion flames of various fuel types. The detector processes multiple signal data collected through its unique time-domain and frequency-domain signal processing and Fourier fuzzy algorithm. By comprehensively judging and processing in combination with the interference source logic, it can eliminate the interference of ambient light and heat body radiation, and can maximally suppress false alarms. It is very suitable for indoor or outdoor open-air environments with multiple false alarm sources. The special fire signal processing algorithm and multi-sensor technology greatly improve the sensitivity of the detector, enabling it to work in harsh industrial environments such as high/low temperature and high humidity.


2.Product Features


(1) Multi-frequency infrared + ultraviolet + time domain + frequency domain multiple judgment
(2) Sensitivity:be set on-site.
(3) Self-learning function
(4) Electromagnetic interference resistance
(5) False alarm prevention, solar blind
(6) Patented, industrialized appearance design
(7) Unique field-of-view angle adjustment markings
(8) Dust-proof, explosion-proof, anti-corrosion, and rain-proof design
(9) Complies with the national standard GB 15631 - 2008 "Special Fire Detectors" and GB 12791 - 2006 "Point-type Ultraviolet Flame Detectors"


3. Application 


(1) This detector is applicable to places with smokeless liquid and hydrocarbon fires, as well as those prone to deflagration.
(2) Nuclear power plants, converter stations, transformer areas
(3) The brewing industry, wine storage
(4) Spray painting workshops
(5) Natural gas exploration and production enterprises
(6) The pharmaceutical industry
(7) Paint – manufacturing, storage, transportation
(8) Chemicals – production, storage, transportation
(9) Power plants – pump areas, machine rooms, unattended areas
(10) Petrochemical products – production, storage, and transportation
(11) Large factory warehouses – storage of flammable materials
(12) Printing – solvent handling, flattening, drying processes
(13) Chip production workshops


4.Main Technical Data


Rated voltage 24V DC (18V DC~36V DC)
Operating current ≤20mA
Alarm current ≤25 mA / DC 24 V
Ambient temperature -10~+55 °C
Ambient humidity ≤95% relative humidity without condensation
Spectral response 3.8µm 4.4µm 5.3µm 185-260nm
Response Time N-heptane ≤15s
Adjustable sensitivity Level I (The default level is Level I at the factory and it is locked.)
Detection angle Vertical viewing angle: 90°; Horizontal viewing angle: 120°
Protection level IP67
Output mode Standard relay output (fault, fire alarm)
Relay contact capacity 1A/AC 125V  2A/DC 30V
Material Cast aluminum (stainless steel is optional)
Implementation standard GB15631-2008  GB12791-2006
Dimensions 165mmx136mmx 100m(6.50in×5.35in×3.94in)
Weight 1.35kg (2.976lbs)
Cable outlet thread Standard G3/4, two pieces
Explosion-proof mark Ex db C T6 Gb,Ex tb IIIC T80 Db
Detection distance Fuel Fire source size Details
N-Heptane 0.3mx0.3m(lft.x1ft.) 50m(164ft.)
Petrol 0.3mx0.3m(1ft.x 1ft.) 40m(131ft.)
Diesel fuel 0.3mx0.3m(1ft.x lft.) 35m(114ft.)
Kerosene 0.3mx0.3m(lft.x1ft.) 35m(114ft.)
Ethanol 0.3mx0.3m(lft.x lft.) 30m(98ft.)
Methane 0.5mx0.2m(1.7ft.x0.7ft.) 30m (98ft.)
Sheet of paper 0.3mx0.3m(1ft.x 1ft.) 25m(82ft.)


Quad Band Flame Detector UV IR 24V DC CNEX For Power Plants 1


5.Indicator Lights


Status Indicator light
Operation Indicator Light (Green) Always on
Alarm Confirmation Indicator Light (Red) It flashes for early warning and stays on when in alarm.
Fault Indicator Light (Blue) When a fault occurs, the blue light stays on (and the red light goes out). When the device is powered on, it flashes, indicating the self-checking and self-adaptive status.


6.Complete Product Set


Quad Band Flame Detector UV IR 24V DC CNEX For Power Plants 2


Name  Quantities Unit of measure
JSY-F401
Point-type Infrared Flame Detector
Point-type Ultraviolet Flame Detector
1 piece
Instruction Manual 1 copy
Explosion-proof Certificate 1 copy
Mounting Bracket 1 item
Fastenings 1 item
M8 Nut 1 piece
M8x45 Hexagon Socket Head Cap Screw 1 piece
M8x25 Hexagon Socket Head Cap Screw 1 piece
Flame Detection Remote Controller YC-F1 1 piece per batch